Product Details:
|
In: | 6,10,16,20,25,32,40A | Install: | Din Rail |
---|---|---|---|
Brand: | SONTUOEC | Type: | Electrical |
Model: | A, AC | Breaking Capacity: | 6KA |
Name: | Rcbo Device | Price: | RCBO Price |
Size: | 18mm Width RCBO 2P | ||
Highlight: | Din Rail Type RCBO Circuit Breaker,6ka RCBO Circuit Breaker,18mm Width RCBO Circuit Breaker |
STRO4-40L series RCBO earth leakage circuit breaker ELCB provide the function of isolation switching and earth leakage protection of electrical circuits.And also provide the indirect protection of the operator's body against the dangerous effects of electric currentof and provide the protection the fire caused by the electrical circuits fault.The rated voltage 230V ,and rated current from 6A to 40A.It complys with IEC/EN61009.1.
Sandard | IEC/EN61009-1 | ||
Electrical features |
Type(wave form of the earth leakage sensed) | Electronic type | |
Rated current In | A | A,AC | |
Poles | P | 1P+N | |
Rated voltage | V | AC 230 | |
Rated Current : | 6,10,16,20,25,32,40A | ||
Rated sensitivity I△n | A | 0.01,0.03,0.1,0.3,0.5 | |
Insulation voltage Ui | V | 500 | |
Rated residual making and breaking capacity I△m |
A | 630 | |
Short-circuit current I△c | A | 6000 | |
SCPD fuse | A |
|
|
Rated frequency | Hz | 50/60 | |
Pollution degree | 2 | ||
Mechanical features |
Electrical life | t | 4000 |
Mechanical life | t | 10000 | |
Protection degree | IP20 | ||
Ambient temperature (with daily average ≤35℃) |
℃ | -25~+40 | |
Storage temperature | ℃ | -25~+70 | |
Installation | Terminal connection type | Cable/U-type busbar/pin-type busbar | |
Terminal size top/bottom for cable | mm2 | 25 | |
AWG | 18-3 | ||
Terminal size top/bottom for busbar | mm2 | 25 | |
AWG | 18-3 | ||
Tightening torque | N*m | 2.5 | |
In-lbs | 22 | ||
Mounting | On DIN rail EN 60715(35mm)by means of fast clip device | ||
Connection | From top and bottom |
Wenzhou Santuo Electrical Co.,Ltd. Browse Categories
RCBO Circuit Breaker
RCCB Circuit Breaker
MCB Circuit Breaker
MCCB Circuit Breaker
ELCB Circuit Breaker
AC Contactor
Magnetic Contactor
Air Conditioning Contactors
Thermal Overload Relay
Magnetic Starter
Electrical Isolator Switch
Contact Person: Mr. Sunny Zhang
Tel: 86-13868610160
Fax: 86-577-67235072